Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Minimum 1 hr Critical Load (kW) Average 1 hr Critical Load (kW) Average Daytime 1 hr Critical Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 634 789 1,493 1,913 2,713 60 178 248 306 0 101 0 1,223 0 0 158 264 0 612 2,094 24 4,999 24 251 46,590 3,419,904 2,095,593 1,550,989
mg1 675 789 1,493 1,913 2,713 211 403 498 713 0 345 0 2,852 0 0 375 926 0 1,426 4,998 56 2,911 56 1,844 111,497 7,908,791 4,790,125 2,964,482
Summary None 789 1,493 1,913 2,713 271 581 746 1,019 0 446 0 4,075 0 0 533 1,190 0 2,038 7,092 40 7,910 40 251 158,087 11,328,695 6,885,718 4,515,471

Report Generated

2024-07-30 13:27:53.874862

User Warnings

Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Component Count Cost Estimate ($)
mg0 mg0 Microgrid Design 1 100,000
mg0 mg0 Microgrid Controls 1 100,000
mg0 632633 SCADA disconnect switch 1 50,000
mg0 634a_data_center AMI disconnect meter(s) 1 300
mg0 634b_radar AMI disconnect meter(s) 1 300
mg0 634c_atc_tower AMI disconnect meter(s) 1 300
mg1 mg1 Microgrid Design 1 100,000
mg1 mg1 Microgrid Controls 1 100,000
mg1 671692 SCADA disconnect switch 1 50,000
mg1 675a_hospital 3-phase relay(s) 1 20,000
mg1 675b_residential1 3-phase relay(s) 1 20,000
mg1 675c_residential1 3-phase relay(s) 1 20,000
mg1 692_warehouse2 3-phase relay(s) 1 20,000

Description